TRIPPING CURRENT RANGES OF OVERLOAD AND SHORT-CIRCUIT PROTECTIVE DEVICE FOR LV CIRCUIT BREAKER

Posted by enal Minggu, 05 Agustus 2012 0 comments



Tipe of protective relay
Over Load Protection
Short Circuit protection
Domestic Breakers IEC 60898
Thermal magnetic
Ir  = In
Low Setting
Tipe B
3 In Im<5In
Standard setting Tipe C
5 In Im<10 In
High Setting circuit Tipe D
5 In Im<20In (*)

Modular industrial Circuit breaker
Thermal  magnetic
Ir = In
Fixed
Low setting
Tipe B or Z
3,2 In< fixed < 4,8 In
Standard Setting tipe C
7 In < fixed< 10 In
High Settinf
Tipe D or K
10 In <fixed<14 In
Industrial (**)Circuit Breakers
IEC 60947-2
Thermal Magnetic
Ir = In Fixed
Fixed : Im=7 to 10 In

Adjustable :
0,7 In Ir<In
Ajustable :
-Low setting : 2 to 5 In
-standard Setting : 5 to 10 In
Electronic
Long  delay
0,4 In Ir In
Short-delay,adjustable
1,5 Ir Im<10 Ir
Instantantaneous (I)fixed
I=12 to 15 In

* 50 In in IEC 60898 ,Wich is considered to be unrealistically high by most European manufacturers(M-G = 10 to 14 In)
** For industrial use,IEC standards do not specity values. The above value are given only as  being those in common use.
Sumber : Electrical Installation guide- Schneider Electric

Jika Anda Berkenan, Bagilah informasi ini kepada teman-teman Anda

Categories:
TERIMA KASIH ATAS KUNJUNGAN ANDA
Judul: TRIPPING CURRENT RANGES OF OVERLOAD AND SHORT-CIRCUIT PROTECTIVE DEVICE FOR LV CIRCUIT BREAKER
Semoga artikel ini bermanfaat bagi anda. Jika ingin mengutip, baik itu sebagian atau keseluruhan dari isi artikel ini harap menyertakan link dofollow ke http://www.jasaelektrikal.com/2012/08/tripping-current-ranges-of-overload-and.html. Terima kasih sudah singgah membaca artikel ini.

0 comments:

Posting Komentar


Find Us Social Media




Entri yang Diunggulkan

Perakitan Panel Capasitor Bank

Suatu instalasi Listrik gedung,pabrik,tambang memerlukan panel capacitor Bank untuk memperbaiki atau menghindari  transforma...

Entri Populer

Hubungi Kami

Nama

Email *

Pesan *